Unscrew the terminal to its widest position before insertion.
| Parameter | Specification | | ----------------------- | ----------------------------------------------------------- | | | M91-T4-R6-ZK1 | | I/O Configuration | 12 Digital Inputs (24VDC) 6 Relay Outputs 2 Analog Inputs | | Display | 2x16 Character, STN LCD, Backlit | | Keypad | 15-key Membrane Keypad | | High-Speed Input | 1 Channel (10 kHz) for counting or shaft-encoding | | Analog Resolution | 10-bit | | Program Memory | 36K Ladder Code | | Communications | 1 x RS232/RS485 (Software Selectable) | | Power Supply | 24VDC | | Protection Rating | IP65 / NEMA4X (Front Panel) | | Mounting | DIN-rail | | Weight | Approx. 1.35 kg | M91-t4-r6-zk1 Manual
Built primarily as a proprietary controller option for specialized air-treatment networks, including ZEKS Compressed Air Solutions. Unscrew the terminal to its widest position before insertion
M91-T4-R6-ZK1
| Problem | Check | |---------|-------| | No output | Supply voltage, output type (sink/source), fuse (if present) | | Input not reading | Wiring polarity, jumper setting (NPN/PNP) | | Can’t connect | COM port, cable (null modem), baud rate (115200 default) | M91-T4-R6-ZK1 | Problem | Check | |---------|-------| |
Route low-voltage signal, communication, and sensor wires in separate conduits away from high-voltage AC power lines to eliminate crosstalk. 4. System Configuration and Programming